久久国产精品无码网站_3D动漫同人精品无码专区_亚洲AV永久无码精品网址_无码天堂亚洲国产AV

High voltage disconnect switches

PRODUCT

CONTACT US

Tel:400-685-8582

Tel:+86-21-57715555
           +86-21-37831986

Fax:+86-21-37831846

Phone:

Email:weho@chinaweho. com

 Address:Building 2, No.8 Nanle Road, Songjiang District, Shanghai

GN19 isolating switch

GN19 isolating switch GN19 isolating switch

GN19 isolating switch

  • Category:High voltage disconnect switches
  • I. Overview GN19-10 (GN19-10C) series indoor high-voltage isolating switch is suitable for AC 5Hz, rated working voltage 6, 10kv; rated working current 200, 630, 1250A power system. It is used as indoor switchgear for breaking and closing the circui
  • Hotline:   
Product Description

I. Overview

 GN19-10 (GN19-10C) series indoor high-voltage isolating switch is suitable for AC 5Hz, rated working voltage 6, 10kv; rated working current 200, 630, 1250A power system. It is used as indoor switchgear for breaking and closing the circuit under the condition of voltage and no load. This isolating switch is equipped with CS6-1 manual operating mechanism.

 Two: Model and meaning/public/uploads/20201204/201204161Q05W.png It should be noted that among the GN19-10 indoor high-voltage isolating switch models, the forms are divided into GN19-10 flat-mount structure type; GN19-10C is a wall-penetrating type (with casing ); of which: C1--rotate on the casing side C2--break on the casing side, C3--both sides are casing. The GN19-10Y flat-pack structure is equipped with a live display device type. The common models are as follows: GN19-10A400A GN19-10/630A GN19-10/1000A GN19-10/1250A GN19-10C/400A GN19-10C/630A GN19-10C/1000A GN19-10C/1250A

Three: main technical parameters

 Model Rated Working Voltage (KV) Maximum Working Voltage (KV) Rated Working Current (A) Dynamic Stable Current (Peak) (KA) 2S Thermal Stable Current (KA) GN19-10/400-12.5 10 11.5 400 31.5 12.5 GN19-10 / 630-20 10 11.5 630 50 20 GN19-10 / 1000-31.5 10 11.5 1000 80 31.5 GN19-10 / 1250-40 10 11.5 1250 100 40 GN19-10C / 400-12.5 10 11.5 400 31.5 12.5 GN19-10C / 630 -20 10 11.5 630 50 20 GN19-10C/1000-31.5 10 11.5 1000 80 31.5 GN19-10C/1250-40 10 11.5 1250 100 40

Four: appearance and installation dimensions

 Dimensions of GN19-10 Indoor High Voltage Isolation Switch Installation Dimensions of GN19-10 Indoor High Voltage Isolation Switch

Five: structure and working principle

 The conductive part of each phase of the GN19-10/400A, GN19-10/630A, GN19-10/1000A, GN19-10/1250A indoor high-voltage isolating switch is fixed on the base through two post insulators. (For GN19-10C/400A, GN19-10C/630A, GN19-10C/1000A, and GN19-10C/1250A, one is a pillar insulator and the other is a porcelain bushing insulator) It consists of static contacts and contact bases (or conductive rods). A pull rod insulator is connected in the middle of each phase contact knife, and the pull rod insulator is connected with the main shaft installed on the base. The main shaft is connected with the connecting rod and the CS6-1 hand force mechanism through the handle. The contact blade is composed of two grooved copper plates, which not only increases the heat dissipation area of the contact blade, which is beneficial to lowering the temperature, but also improves the mechanical strength of the contact blade and improves the dynamic stability of the switch. One end of the contact knife is mounted on the contact seat (or on the conductive rod) by means of bolts. In order to rotate the contact blade, the other end is separably connected with the static contact blade, and the contact force of the contact blade is maintained by the springs at both ends. Here, the indoor high-voltage isolating switch is arranged with a magnetic lock plate at the contact point. The purpose of adding the magnetic lock plate is to strengthen the attraction between the two slot-shaped contacts when a large short-circuit current passes through, that is, to increase the contact pressure, thus improving the dynamic and thermal stability of the switch. GN19-10/400A and GN19-10/630 isolation switch poles have small passing current. Therefore, the structure does not need to add a magnetic lock plate. Base assembly: It consists of base, spindle, limiter, stop ring, etc. The limiter is mainly used to ensure the required end position when the conductive contact knife is opened and closed.